Plate filter
The pre-filtering of the air-conditioning filter system can extend the service life of medium and high efficiency;
Clean room inlet and return air filtration;
Pre-filtering with large air compressor.
characteristic:
Low initial pressure and large dust holding capacity
The filter material composite metal mesh is made into a foldable type; its filter area is 5 times that of a general flat filter, and the cardboard or metal frame is easy to replace;
Comply with fire protection classification standard European DIN53438-F1 and American UL900-class1;
Strong humidity resistance, which can reach 100% relative humidity;
Temperature resistance up to 80℃;
The size can be customized according to user requirements.
Metal frame can be reused
Performance parameters:
name |
|
Flat filter |
Pleated filter |
||
Frame thickness |
(mm) |
24 |
|
46 |
96 |
Filter level |
|
G3(EU3) |
G4(EU4) |
G4(EU4) |
F5(EU5) |
Average capture rate |
(%) |
76 |
85 |
91.3 |
97.4 |
Rated air volume |
(m3/h) |
5400 |
5400 |
3400 |
5400 |
Initial pressure |
(Pa) |
20 |
30 |
67 |
96 |
Recommended final pressure |
(Pa) |
450 |
450 |
450 |
600 |
Frame material |
|
Paper frame or metal frame |
Paper frame or metal frame |